Partner Manufacturers - Product Information

PX3-4917-V2 - Raritan Outlet Metered iPDU (3-Phase): 3PH Wye, 400V AC, 32A, 24 Outlets: 12x IEC C13, 12x IEC C19, Plug: IEC 60309 32A 3P+N+PE, 22.2kVA, Zero U, R-Controller, LCD Display, 2x USB-A/B, Serial, Ethernet and Sensor Port (PX-4000 Series) BTO


Description:
The Raritan PX-4000 family of high-quality rack power distribution units (PDUs) offers real-time remote unit-level and individual outlet-level power monitoring of current (amps), voltage, power (kVA, kW), power factor and energy consumption (kWh) with ISO/IEC +/- 1% billing-grade accuracy. The PX-4000 also supports Raritan’s plug-and-play environmental sensors. Users can define thresholds and receive alerts when thresholds are crossed for both power and environmental events.

The PX-4000 series is available in Zero U (vertical mount) and 1U and 2U (horizontal mount) form factors with a wide variety of NEMA, IEC and other plugs and receptacles, including models which support high power distribution such as 400V. Precise power information can be monitored, and the PX-4000 configured, via a user-friendly Web browser GUI or command line interface. Power information is also displayed at the PDU locally. Security is ensured with up to 256-bit encryption, strong passwords and advanced authorization options, including permissions, LDAP/S and Active Directory. Plus the PX-4000 series is fully compatible with Raritan's Power IQ energy management software solutions.

Features:
Energy Metering Voltage (V), Current (A), Active Power (kW), Real Power (kVA), Energy (kWh), Power Factor
Metering Accuracy ISO/IEC 62053-21 1%
Metering per Input Line Yes
Metering per Branch Circuit Breaker Yes
Metering per Output Receptacle Yes
Remote Outlet Switching No
Environmental Sensor Ready Yes
Networking 10/100 BaseT Ethernet. Optional WiFi (802.11a/b/g/n)
Remote Management HTTP(s); SSH; Telnet; RS-232 (Serial); Power IQ; SNMP version v2/v3; SMTP; JSON-RPC
Cascading Yes
Max 8 PDUs can be daisy chained using a single Ethernet connection
Onboard Display User-selectable display (voltage, current, or active power:per line, per breaker, or per receptacle)
Compatible Sensors: Temperature, Humidity, Air Flow, Static Pressure, Single cable connection provides temp/humidity monitoring at three points in cabinet (with a single sensor assembly)
Replaceable controller

PLUG: IEC 32AIND309 (3 PHASE)

Specification:
PX3-4917-V2 - Raritan Outlet Metered iPDU (3-Phase): 3PH Wye, 400V AC, 32A, 24 Outlets: 12x IEC C13, 12x IEC C19, Plug: IEC 60309 32A 3P+N+PE, 22.2kVA, Zero U, Replaceable Controller with LCD Display, 2x USB-A, USB-B, Serial, Ethernet and Sensor Port (PX-4000 Series)

BTO - (BUILT TO ORDER)

INPUT

Input Plug IEC 60309 3P+N+E 6h 32A 4P5W (L1/L2/L3/N/E)
IP44("splashproof") (400V, 3 phase)
Cord Length 3 meters (9.84 feet) standard
Cord Entry Bottom-front feed
Cable Type 4P 5W
Number of Power Cords 1
Maximum Input Current 32A (per line)
Nominal Input Voltage 400V, 3 phase
Rated Input Voltage 380 - 415V, 3 phase
Input Frequency 50/60Hz
Power Capacity 21.1kVA at 380V, 23.0kVA at 415V

OUTPUT

Nominal Output Voltage 230V
Rated Output Voltage 220 - 240V
Output Connections a. (12) IEC 60320 C13 2-pole, 3-wire; 10A
b. (12) IEC 60320 C19 2-pole, 3-wire; 16A
Overload Protection (6) 16A 1-pole LEGBXA6-16 circuit breaker
Cable Retention Raritan SecureLockTM Ready
Optional retention clips are also available

PHYSICAL

Unit Dimensions (W x D x H) 2.1" x 2.6" x 70.1" ; 52mm x 65mm x 1780mm
Shipping Dimensions (W x D x H) 11.22" x 4.53" x 75.39" ; 285mm x 115mm x 1915mm
Colour - Black powder coat
Mounting - G2-RACK-FOR-ZU

ENVIRONMENTAL

Operating Environment 5 - 60°C (41 - 140°F)
Operating Relative Humidity 5-85%
Operating Elevation 0-10000ft

CONFORMANCE

Regulatory Approvals CE, Canada ICES-003, Class A Part 15 Class A of the FCC rules RoHS

Click here for further information